Explosion protection:
II 2G EEx de IIC T6
Zone:
1
Certificates:
PTB 03 ATEX 1155
Protection class to EN 60 529:
IP 56
Ambient temperature:
-50°C up to +100°C
Voltage:
max. 690 V
Rated current:
- 2,5mm²: max. 22A
- 4,0mm²: max. 30A
- 6,0mm²: max. 39A
Material:
Brass
Equipment:
- 2 terminal blocks 4mm²
- Cable gland M 24x1,5, internal parts Z14
- Position of cable entries is exchangeable
Variations:
Cable gland M 18x1,5, M 20x1,5 or M 25x1,5, internal parts W or Z
Terminals/Poles Logo:
1mm² up to 6mm², 4-pole + 2 PE
Pole Capacity:
- 3 x 6mm² single wire
- 3 x 4mm² fine wire
- 4 x 4 mm² single wire
Junction boxes, brass, T6, Ignition protection 'e'