Junction Box T6


On-off switches, brass, T6, Ignition protection 'de'

Explosion protection:

II 2G EEx de IIC T6


Zone:

1


Certificates:

PTB 03 ATEX 1159


Protection class to EN 60 529:

IP 56


Temperature range:

-55°C to +65°C


Rated insulation voltage:

max. 750 V


?????????:

max. 690 V


Rated normal current:

max. 16 A


Rated impulse withstand voltage:

max. 6 kV


Utilisation category:

- 16A / 690V: AC 1

- 8A / 500V: AC 3

- 4A / 690V: AC 3

- 16A / 415V: AC 15


Material:

Brass


Rated connection capacity:

- Fine wire: 1,5 to2,5 mm²

- Single wire: 1,5 to 4 mm²


Switch:

Ex switch interior, 2-pole, On-Off


Equipment:

Cable gland M 24x1,5, internal parts Z14


Variations:

.../S = multi-circuit switch, 1-pole


.../We = chance-over switch, 1-pole


Other switch types on- Cable gland M 18x1,5, M 20x1,5 or M25x1,5 equipment W or Z request


3 or 4 cable glands



Other related products